AWG to mm²

12 AWG wire has a cross-section of 3.309 mm² and a diameter of 2.053 mm. Pick any gauge to get its area, diameter and copper resistance, or type an area in mm² to find the matching gauge.

  • Free
  • No sign-up
  • Runs in your browser

By Maaz Zindani · Updated

Convert
For the copper resistance. Leave 20 for the table value.
12 AWG in mm²

3.309 mm²cross-section of a 12 AWG solid wire

  • Diameter 2.053 mm (0.0808 in)
  • 6,530 circular mils
  • 6.53 kcmil
  • Area (mm²)3.309
  • Diameter (mm)2.053
Copper resistance, 20 °C
5.211 Ω per km
Per 1,000 ft
1.588 Ω
Area in square inches
0.005129

Formula: d = 0.127 mm × 92^((36 − gauge) ÷ 39); area = π × d² ÷ 4

Your numbers: 0.127 × 92^((36 − 12) ÷ 39) = 2.0525 mm; π × 2.0525² ÷ 4 = 3.3088 mm²

  • Resistance is for solid annealed copper. This page gives no current rating: take that from the wiring rules where you work.
Neighbouring gauges, solid copper at 20 °C
AWGDiameter (mm)Area (mm²)Ω per km
102.5885.2613.277
112.3054.1724.132
122.0533.3095.211
131.8282.6246.571
141.6282.0818.285

How to use the Wire Gauge Converter

  1. Choose AWG to mm² to start from a gauge, or mm² to AWG to start from a metric cross-section.
  2. Pick the Gauge from the list, or type the Cross-section in square millimetres.
  3. Change the Wire temperature if you want the copper resistance at a warmer or colder wire.
  4. Read the area or the gauge, the diameter, the circular mils and the neighbouring sizes in the table.

How do you convert AWG to mm²?

Work out the diameter from the gauge number, then the area of a circle with that diameter. The American Wire Gauge fixes two sizes: No. 0000 is 0.4600 inch and No. 36 is 0.0050 inch across. The 38 sizes between them follow a geometric progression, so each gauge is thicker than the next by the same factor, the 39th root of 92, which is 1.1229322.

That gives one formula for any gauge: diameter = 0.127 mm × 92^((36 − gauge) ÷ 39), where 0.127 mm is the 0.0050 inch of No. 36. Then area = π × diameter² ÷ 4. For 12 AWG the diameter is 2.0525 mm and the area is 3.3088 mm². For 10 AWG they are 2.5882 mm and 5.2612 mm².

The thick sizes are written with zeros. 1/0 (one aught) is gauge 0, 2/0 is 00, 3/0 is 000 and 4/0 is 0000, so in the formula they count as 0, −1, −2 and −3. 4/0 works out at 11.684 mm, which is the 0.4600 inch the gauge starts from.

US tables also give the area in circular mils: the diameter in thousandths of an inch, squared. It skips π, so it is a quick way to compare wires. 12 AWG is 6,530 circular mils. Cable larger than 4/0 is sold by area in kcmil, thousands of circular mils, rather than by a gauge number.

AWG sizes: solid copper wire at 20 °C
AWGDiameter (mm)Area (mm²)Circular milsΩ per km
4/011.684107.2211,6000.1608
2/09.26667.43133,0770.2557
1/08.25153.48105,5350.3224
26.54433.6366,3710.5127
45.18921.1541,7410.8152
64.11513.326,2511.296
83.2648.36616,5102.061
102.5885.26110,3833.277
122.0533.3096,5305.211
141.6282.0814,1078.285
161.2911.3092,58313.17
181.0240.8231,62420.95
200.8120.51761,02233.31
220.6440.325564252.96
240.5110.204740484.21
260.4050.1288254133.9
280.3210.08098160212.9
300.2550.05093101338.5

Why does a bigger AWG number mean a thinner wire?

The numbers count drawing steps. Wire is made by pulling it through smaller and smaller dies, and a higher gauge number means more passes, so a thinner wire. That is why 24 AWG is much finer than 12 AWG, and why the thickest sizes ran out of numbers and needed the zeros.

Because the sizes form a geometric series, a few rules of thumb hold across the whole range. Every 3 gauges the area roughly halves: 10 AWG is 5.261 mm² and 13 AWG is 2.624 mm², a ratio of 2.005. Every 6 gauges the diameter roughly halves: 4 AWG is 5.189 mm and 10 AWG is 2.588 mm.

Resistance follows the area, so it doubles every 3 gauges as well. If you know one gauge well, you can estimate the ones around it in your head. The calculator lists the two sizes on each side of your choice for that reason.

To identify an unlabelled solid wire, strip a short length and measure the bare copper with calipers, not the insulation. Halve the diameter, square it and multiply by π to get the area. A bare wire of 1.63 mm gives 2.087 mm², and the mm² to AWG mode turns that into 14 AWG. Measure in two directions and take the average, since a cheap gauge or a squashed wire can be a few hundredths off.

What AWG is 1.5 mm² or 2.5 mm²?

No AWG size matches a round metric size exactly, so there are two useful answers. The nearest gauge by area for 2.5 mm² is 13 AWG (2.62 mm²). The thinnest gauge with at least 2.5 mm² of copper is 13 AWG (2.62 mm²). For 1.5 mm² the nearest is 15 AWG and the thinnest with at least that area is 15 AWG.

The "at least" answer is the one to use when a wire must carry a given current or keep a voltage drop small, because a thinner wire has more resistance. The nearest answer is fine for matching a connector, a crimp or a terminal size. The calculator shows both, plus the exact gauge as a decimal, so you can see how far each choice is from the area you typed.

Do not treat this as a current rating. How much current a cable may carry depends on its insulation, how it is installed, the air around it and the rules where you live. Take that from the wiring code that applies to your job or from a qualified electrician.

Metric cross-sections and their AWG
Metric sizeNearest AWGThinnest AWG with at least that area
0.5 mm²20 AWG (0.518 mm²)20 AWG (0.518 mm²)
0.75 mm²18 AWG (0.823 mm²)18 AWG (0.823 mm²)
1 mm²17 AWG (1.04 mm²)17 AWG (1.04 mm²)
1.5 mm²15 AWG (1.65 mm²)15 AWG (1.65 mm²)
2.5 mm²13 AWG (2.62 mm²)13 AWG (2.62 mm²)
4 mm²11 AWG (4.17 mm²)11 AWG (4.17 mm²)
6 mm²9 AWG (6.63 mm²)9 AWG (6.63 mm²)
10 mm²7 AWG (10.5 mm²)7 AWG (10.5 mm²)
16 mm²5 AWG (16.8 mm²)5 AWG (16.8 mm²)
25 mm²3 AWG (26.7 mm²)3 AWG (26.7 mm²)
35 mm²2 AWG (33.6 mm²)1 AWG (42.4 mm²)
50 mm²1/0 AWG (53.5 mm²)1/0 AWG (53.5 mm²)

How much resistance does a copper wire have?

Resistance per metre is the resistivity of copper divided by the cross-section. The International Annealed Copper Standard sets that resistivity at 0.017 241 Ω·mm²/m at 20 °C. 12 AWG has 3.309 mm², so it has 5.211 Ω per km, or 1.588 Ω per 1,000 feet.

This number gives you the voltage drop of a run. Current goes out on one conductor and back on the other, so a 20 m cable run has 40 m of wire in the loop. In 12 AWG that is 0.208 Ω, and 10 A through it loses 2.08 V. In 10 AWG the same run loses 1.31 V.

Copper resistance rises as it warms, by 0.00393 per degree Celsius from 20 °C. At 60 °C the 12 AWG figure grows to 6.03 Ω per km. Type a temperature in the calculator to apply the same correction to any gauge. The values are for solid annealed copper. Stranded conductors are specified by their total copper area, so compare a stranded cable by its area, not by its outside diameter.

Use it with

Questions

What is 12 AWG in mm²?

3.309 mm², with a diameter of 2.053 mm.

What is 14 AWG in mm²?

2.081 mm², with a diameter of 1.628 mm.

What is 2.5 mm² in AWG?

Nearest by area is 13 AWG (2.62 mm²). The thinnest gauge with at least 2.5 mm² is 13 AWG.

What is 16 AWG in mm²?

1.309 mm², with a diameter of 1.291 mm.

Is AWG the same as SWG?

No. SWG, the British Standard Wire Gauge, uses different diameters for the same numbers, so convert through mm or inches rather than by the number.

Does this page give the current a wire can carry?

No. It gives size and resistance only. Current ratings depend on insulation and how the cable is installed, so check the wiring rules that apply to you.