kVA to amps
Choose single phase or three phase, type the kVA and the voltage, and read the current in amps. You can also run it backwards from amps to kVA.
- Free
- No sign-up
- Runs in your browser
72.17 Athree phase · 50 kVA at 400 V
- Three phase, line voltage
- 50,000 VA
- 72,169 mA
- Amps
- 72.169 A
- kVA
- 50.000 kVA
Your working: I = kVA × 1,000 ÷ (√3 × V) = 50 × 1,000 ÷ (1.732 × 400 V) = 72.169 A.
Cable, breaker and transformer choices belong to a qualified electrician; this figure is the maths only.
How to use the kVA to Amps Converter
- Pick Single phase or Three phase under Supply.
- Under Convert, choose kVA to amps or Amps to kVA.
- Type the Apparent power or the Current, and the Voltage. For three phase, use the voltage between two lines.
- Add a Power factor if you also want the real power in kW.
How do I convert kVA to amps?
For a single-phase supply, multiply the kVA by 1,000 and divide by the volts. A 5 kVA load on 230 V draws 5,000 ÷ 230 = 21.74 A. The kVA figure is already a volts-times-amps number, so no power factor is needed here. That is the difference from converting kW, where the power factor does matter.
The same sum runs backwards: amps times volts, divided by 1,000, gives kVA. A 10 A load on 230 V is 2,300 VA, which is 2.30 kVA. Use the Amps to kVA choice to do this on the page.
How do I convert kVA to amps for three phase?
Three-phase power adds the square root of 3, about 1.732, to the bottom of the sum: amps = kVA × 1,000 ÷ (1.732 × volts). Take a 50 kVA load on a 400 V supply. The current is 50,000 ÷ (1.732 × 400) = 72.17 A in each of the three wires.
Use the voltage measured between two of the three live wires. This is called the line voltage. A figure measured from one wire to neutral is smaller, by the same 1.732, and gives a wrong answer if you type it here. Going the other way, 144 A at 400 V is 100.00 kVA.
| Size | 3-phase 208 V | 3-phase 400 V | 3-phase 480 V | 1-phase 120 V | 1-phase 230 V |
|---|---|---|---|---|---|
| 10 kVA | 27.8 A | 14.4 A | 12.0 A | 83.3 A | 43.5 A |
| 25 kVA | 69.4 A | 36.1 A | 30.1 A | 208.3 A | 108.7 A |
| 50 kVA | 138.8 A | 72.2 A | 60.1 A | 416.7 A | 217.4 A |
| 100 kVA | 277.6 A | 144.3 A | 120.3 A | 833.3 A | 434.8 A |
| 250 kVA | 693.9 A | 360.8 A | 300.7 A | 2083.3 A | 1087.0 A |
Why do generators and transformers use kVA?
Think of a transformer as a pipe. The pipe has to be wide enough for the whole flow, whether or not all of it does useful work. So the maker states the rating in kVA, which is volts times amps, and leaves the power factor to the load. A 25 kVA unit on 400 V three phase can pass 36.08 A, whatever you plug into it.
This also explains why two machines with the same kW can need different supplies. A machine with a poor power factor draws more amps, so it needs a bigger kVA rating. Compare the amps, not just the kW, when you check that a supply can cope.
Start from the nameplate of the machine. If it lists amps and volts, use Amps to kVA to find what the supply must be rated for. A 63 A load on 400 V three phase is 43.65 kVA, so a 50 kVA supply would be too small.
What is the difference between kVA and kW?
kVA is the total power a supply has to carry. kW is the part of it that does real work. The share is the power factor: kW = kVA × power factor. A 50 kVA generator with a factor of 0.8 gives 40 kW of useful power. Both kinds of rating end up as the same current in the wires, because the wires carry the full kVA.
Transformers and generators are sold by kVA because the wire and the winding feel the current, whatever the factor. Heaters are sold by kW because they just make heat. To switch between the two, add the power factor in the optional box on this page and read the kW under the answer.
How many amps does each kVA need at common voltages?
The table gives the current for exactly 1 kVA. Scale it for your own size: 25 kVA draws 25 times as much. The voltages listed are examples, and the supply voltage where you live may differ, so check the nameplate on your equipment.
The three-phase columns in the first table use 208 V, 400 V and 480 V. These are examples of voltages that appear on equipment around the world; the right one is whatever your supply delivers. Type it in and the page does the rest.
Higher voltage means less current for the same kVA. That is why long cables run at a higher voltage: thinner wire can carry the same power.
| Voltage | Single phase | Three phase |
|---|---|---|
| 120 V | 8.333 A | 4.811 A |
| 208 V | 4.808 A | 2.776 A |
| 230 V | 4.348 A | 2.510 A |
| 240 V | 4.167 A | 2.406 A |
| 400 V | 2.500 A | 1.443 A |
| 415 V | 2.410 A | 1.391 A |
| 480 V | 2.083 A | 1.203 A |
Add the amps of all the loads on one feed, then compare the total with the rating of the breaker, with an electrician's guidance.
Use it with
- Watts to Amps Converter: current drawn by a load at a given voltage, DC or AC.
- Electricity Cost Calculator: cost to run any appliance.
- mAh to Wh Converter: battery energy in watt-hours from capacity and voltage.
Questions
How many amps is 1 kVA?
On a single-phase 230 V supply, 1 kVA is 4.348 A. On three phase 400 V it is 1.443 A.
What is the formula for kVA to amps?
Single phase: amps = kVA × 1,000 ÷ volts. Three phase: amps = kVA × 1,000 ÷ (1.732 × volts).
Do I need the power factor to turn kVA into amps?
No. kVA already includes it. The power factor only matters when you start from kW.
How many amps is a 100 kVA transformer?
At 400 V three phase it is 144.3 A. At 480 V it is 120.3 A.
How do I convert amps to kVA?
Single phase: kVA = amps × volts ÷ 1,000. Three phase: multiply by 1.732 as well. 10 A at 230 V is 2.30 kVA.
Which voltage goes in the three-phase formula?
The line voltage, measured between two live wires, such as 400 V.
The tool's results are computed in your browser by the code on this page; the explanations are checked against the tool's own output.