Wire size calculator

15 amps over 30 meters at 120 volts, with a 3% drop allowed, needs 10 AWG copper wire (5.26 mm²). The page picks the smallest gauge whose voltage drop stays inside your limit.

  • Free
  • No sign-up
  • Runs in your browser

By Maaz Zindani · Updated

From the source to the load, not there and back.
Line to line for three phase.
Example: 3. Your rules or the device may need less.
Example: 30. Copper resistance rises with heat.

This finds the smallest copper AWG gauge whose voltage drop stays within your limit. It does not check how much current the wire may safely carry. An estimate, not electrical advice: a licensed electrician sets the final size.

Smallest copper wire for 15 A over 30 m

10 AWG5.26 mm²

  • Drop 2.95 V
  • 2.46% of 120 V
  • Needs at least 4.31 mm²
Drop with this wire
2.95 V (2.46%)
Power lost in the wire
44.2 W
Next size down
12 AWG: 3.91%, over the limit
Allowed drop
3.6 V
Safe current
Not checked here. Usual minimum for 15 A: 14 AWG
Voltage drop for the gauges around the answer
Gaugemm²Ω per kmDrop (V)Drop (%)Within limit
8 AWG8.372.0611.851.55%Yes
10 AWG5.263.2772.952.46%Yes
12 AWG3.315.2114.693.91%No

How to use the Wire Size Calculator

  1. Type the Current in amps, the One way length of the run and the Supply voltage.
  2. Choose meters or feet, and a Circuit of two wires (DC or single phase) or balanced three phase.
  3. Set the Allowed voltage drop and the Wire temperature. Under Gauges offered, keep even AWG sizes or switch to every size.
  4. Read the gauge in the dark panel, then the drop, the power lost in the wire and the table for the gauges around it.

How do I calculate wire size from voltage drop?

Current flowing through a wire loses voltage along the way: drop equals current times resistance. On a two wire circuit the current goes out and comes back, so the length counted is twice the one way run. For 15 A over 30 m the loop is 60 m. Copper has a resistance of 0.017241 ohm square millimeters per meter at 20 °C, so the copper area that gives exactly a 3% drop on 120 V is 0.017241 times 60 times 15, divided by 3.6 volts, which is 4.31 mm².

Wire is sold in steps, so the page takes the smallest AWG gauge with at least that area. By default it offers even gauge numbers only, the sizes usually stocked, and the Gauges offered box switches that to every AWG size. 10 AWG is 5.26 mm², loses 2.95 V (2.46%) and wastes 44.2 W as heat in the cable. The next size down in the list, 12 AWG, is over the limit, and so is 11 AWG with 3.1%. The table shows what the same 15 A needs as the run gets longer.

Smallest copper gauge for 15 A at 120 V with 3% drop
One way lengthGaugeArea (mm²)
10 m14 AWG2.08
20 m12 AWG3.31
30 m10 AWG5.26
50 m8 AWG8.37
75 m6 AWG13.3
100 m4 AWG21.15

How does the current change the wire size?

Drop grows in step with current, so doubling the amps doubles the copper you need for the same length. At 30 m and 120 V, 5 A is fine on a thin conductor, while 40 A needs a heavy cable. Low voltage circuits suffer most, because a drop that is small next to 120 V is large next to 12 V. On a 12 V run, 20 A over 100 feet needs 2/0 AWG to stay within 3%.

Smallest copper gauge for 30 m at 120 V with 3% drop
CurrentGaugeArea (mm²)
5 A14 AWG2.08
10 A12 AWG3.31
15 A10 AWG5.26
20 A8 AWG8.37
30 A6 AWG13.3
40 A6 AWG13.3

Why does temperature and three phase change the answer?

Copper resistance rises about 0.393% for each degree above 20 °C. Entering a wire temperature of 60 °C raises the drop of the same 10 AWG run from 2.95 V to 3.41 V. A warm cable run in a hot space needs more margin than a cool one, so type a temperature that matches your case.

On a balanced three phase circuit the line to line drop is the square root of 3 (about 1.732) times current, resistance and one way length, instead of the factor 2 of a two wire run. For 30 A over 100 m at 400 V the page gives 8 AWG, with a drop of 10.71 V.

A small warning chip appears when the gauge the page picks is thinner than the usual minimum for the current you typed, for example 14 AWG for 15 A. That hint is a rough rule of thumb for copper building wire and the page does not check safe current, so treat a thin result as a prompt to ask an electrician.

This page checks voltage drop only. How much current a wire may carry without overheating depends on its insulation, how it is installed and the electrical rules where you live, and none of that is calculated here. The result is an estimate and not electrical advice. A licensed electrician should confirm the wire size and the breaker before anything is installed. For gauge sizes use AWG to mm², and for current from power use watts to amps.

How do the AWG gauge numbers relate to each other?

A bigger gauge number means a thinner wire, and the steps are not linear. Every 3 gauge numbers the copper area doubles and the resistance halves: 10 AWG is 5.26 mm² and 7 AWG is 10.55 mm², about twice as much. Every 6 numbers the diameter doubles. This is why the answer jumps quickly when a run gets longer or the current rises.

Gauges at the heavy end are written 1/0, 2/0, 3/0 and 4/0, and the page covers them up to 4/0. If the table says a run needs more than that, the cable is sized in mm² or kcmil, or the load is split over parallel cables, which is a job for the person designing the circuit.

Use it with

Questions

What wire size do I need for 15 amps?

It depends on the length and the voltage. At 120 V over 30 m with a 3% drop limit, the page gives 10 AWG. A shorter run needs a thinner wire, and the safe current rating is a separate check.

What voltage drop is acceptable?

That is your decision or your local rules. The page starts at 3% as an example. Type the limit that applies to you, and use a lower figure for sensitive equipment.

Why do you count the length twice?

On a two wire circuit the current flows out on one wire and back on the other. The loop is twice the one way length, so the resistance doubles. Three phase uses the square root of 3 instead.

Is a bigger wire always better?

A larger gauge lowers drop and heat, but costs more and is harder to fit into terminals. The table shows how much each step saves, so you can see when the gain is small.

Does the page cover aluminum wire?

No. It uses annealed copper only, with the resistance from the AWG table. Aluminum conducts less per mm², so it needs a larger area.

Can I use this to pick a breaker?

No. The breaker protects the wire from overheating, and that depends on the safe current of the wire, which this page does not calculate. Ask a licensed electrician.

The tool's results are computed in your browser by the code on this page, using the sources listed above; the explanations are checked against the tool's own output.